Conductor: Annealed bare solid copper conductor

Insulation: PVC Type-A compound of IS 5831:1984. Insulation color shall be as per customer specification.

Core Formation: The insulated cores shall be laid up together with suitable lay. The outer most layer shall have right hand lay and the successive layers shall be laid with opposite lay. A polyester tape of suitable thickness shall be helically applied normally in cables with double steel tape.

Inner Sheath: Type- ST1 as per IS 5831:1984.

Armouring: Armouring shall consist of the either Galvanised Round Wire/Double Steel Tape.

Outer Sheath: Type- ST1 as per IS 5831:1984

Features

  • Availability of conductor sizes ranging from 1.50 sq.mm to 6.00 sq.mm

  • Suitable for use on AC systems (Earthed or unearthed) for rated
    voltage upto 1100 volts

  • Suitable for use on DC systems for rated voltage upto 1500 volts

Technical Specifications

Nominal Cross sectional areaNo. of Wires in ConductorsNom. Dia of WireMax. Resistance at 20°C
Multi CoreSingle Core
SqmmNo(s)mmΩ/KmΩ/Km
1.011.1317.68918.04
1.511.411.5411.77
2.511.806.9787.118
2.531.066.8436.980
412.244.5064.596
470.854.5914.683
612.82.8842.942
1071.41.6601.693
1671.701.1241.149
2572.240.64840.6614
3572.500.52050.5309
50191.80.37060.3780
Insulation Resistance (M-Ω/Km) (Dry) (500 V DC for 1 Min. at 50°C)10 M-Ω/Km upto 2.5 mm2 Conductor 5 M-Ω/Km More than 2.5 mm2 Conductor
Insulation Resistance (M-Ω/Km) (Wet) (500 V DC for 1 Min. at 50°C)7.5 M-Ω/Km upto 2.5 mm2 Conductor 5 M-Ω/Km More than 2.5 mm2 Conductor
HV Test at Room Temp.4 KV AC (rms) or 12 KV DC (for 5 Min.)


Comment